Furnish cable operated remote controlled volume dampers in inaccessible branch ducts feeding
continuous linear diffuser plenums and where otherwise indicated. Reference architectural drawings for
locations of gypsum board, spline etc. ceilings. Dampers shall be adjustable through the diffuser face
with standard tools, providing positive balancing of multiple airflows to maintain design air throw and
noise criteria. Galvanized steel radial damper shall be direct actuated by a brass plated rotary cable
which is fixed at the damper end in an integral support bracket. Rotary cable shall have a minimum
torque service factor of 200% when installed in accordance with manufacturer furnished instructions.
Entire assembly shall be furnished as one piece for installation with no linkage adjustment required or
miscellaneous small parts. Each unit shall be factory tested as a complete assembly prior to shipment
(100% testing). Accessible cable end shall be secured with a factory furnished nylon clamp, allowing
maximum placement flexibility. Positive, direct, two-way damper control shall be provided without
sleeves, springs, or screw adjustments (that may loosen after ceiling closure). Cable operated dampers
shall be Metropolitan Air Technology LLC. Model #RT-150.